Skip to content

What Size Wire for a 40 Amp Breaker?

A 40 A breaker needs 8 AWG copper or 8 AWG aluminum with 75°C terminations (NEC Table 310.16). Longer runs may need a size up for voltage drop — distances below.

Minimum wire size for 40 amps

ApplicationCopper (75°C)Aluminum (75°C)
Branch circuit / feeder (Table 310.16)8 AWG8 AWG

Assumes 75°C-rated terminations (NEC 110.14(C)) and no more than three current-carrying conductors in a raceway at 30°C ambient. Derating, continuous loads, and local amendments can change the answer — confirm with a licensed electrician.

How far can you run it? (voltage drop)

Keeping voltage drop under the recommended 3% at a 32 A load (80% of the breaker), 8 AWG copper is good for roughly:

System voltageMax one-way run (8 AWG Cu)
120 V71 ft
240 V143 ft

Past these distances, step up one gauge. Run your exact length and load through the voltage drop calculator.

What runs on 40 amps

  • Electric range
  • 32 A EV charger
  • Larger AC condensers

Common receptacle at this rating: NEMA 14-50.

Frequently asked questions

8 AWG copper with 75°C terminations (NEC Table 310.16). In aluminum, use 8 AWG. Longer runs, high ambient temperatures, or bundling can require upsizing.

Ask AI about this

Open an AI assistant with a question grounded in this page.

Full wire & breaker chartVoltage drop calculatorEV charger breaker sizing

Other amperages