kVA to Amps Calculator

Convert kVA to amps — the full-load current — for single- and three-phase systems. Built for sizing transformers, generators, and feeders, it also shows the NEC breaker and copper wire the load needs.

Phase

Full-load current

208.2 A

Apparent power
75 kVA
System
208 V 3-phase

NEC wire & breaker for this load

Breaker
300 A
Min. copper wire (75°C)

Sized at 125% for a continuous load (NEC 210.19/215.2): 208.2 A × 1.25 = 260.2 A.

Copper, 75°C terminations, NEC Table 310.16. Real installs may need derating for ambient heat, conduit fill, or voltage drop. Full wire & breaker chart. Always confirm with a licensed electrician + local AHJ.

Frequently asked questions

Single-phase: amps = kVA × 1,000 ÷ volts. Three-phase: amps = kVA × 1,000 ÷ (1.732 × line-to-line volts). kVA is apparent power, so no power factor is involved. Example: 75 kVA at 208V three-phase ≈ 208 amps.