Skip to content

What Size Wire for a 15 Amp Breaker?

A 15 A breaker needs 14 AWG copper with 75°C terminations (NEC Table 310.16). Longer runs may need a size up for voltage drop — distances below.

Minimum wire size for 15 amps

ApplicationCopper (75°C)Aluminum (75°C)
Branch circuit / feeder (Table 310.16)14 AWGnot typical
Worth knowing: 14 AWG copper is capped at a 15 A breaker by NEC 240.4(D) even though the 75°C table allows more.

Assumes 75°C-rated terminations (NEC 110.14(C)) and no more than three current-carrying conductors in a raceway at 30°C ambient. Derating, continuous loads, and local amendments can change the answer — confirm with a licensed electrician.

How far can you run it? (voltage drop)

Keeping voltage drop under the recommended 3% at a 12 A load (80% of the breaker), 14 AWG copper is good for roughly:

System voltageMax one-way run (14 AWG Cu)
120 V47 ft
240 V95 ft

Past these distances, step up one gauge. Run your exact length and load through the voltage drop calculator.

What runs on 15 amps

  • Lighting circuits
  • Bedroom & living-room outlets
  • Smoke detectors

Common receptacle at this rating: NEMA 5-15.

Frequently asked questions

14 AWG copper with 75°C terminations (NEC Table 310.16, with the NEC 240.4(D) small-conductor cap applied). Aluminum is rarely used at this rating. Longer runs, high ambient temperatures, or bundling can require upsizing.

Ask AI about this

Open an AI assistant with a question grounded in this page.

Full wire & breaker chartVoltage drop calculatorHome electrical load calculator

Other amperages