Skip to content

What Size Wire for a 25 Amp Breaker?

A 25 A breaker needs 10 AWG copper with 75°C terminations (NEC Table 310.16). Longer runs may need a size up for voltage drop — distances below.

Minimum wire size for 25 amps

ApplicationCopper (75°C)Aluminum (75°C)
Branch circuit / feeder (Table 310.16)10 AWGnot typical
Worth knowing: 12 AWG would carry 25 A in the 75°C column, but NEC 240.4(D) caps it at 20 A — so a 25 A breaker needs 10 AWG copper.

Assumes 75°C-rated terminations (NEC 110.14(C)) and no more than three current-carrying conductors in a raceway at 30°C ambient. Derating, continuous loads, and local amendments can change the answer — confirm with a licensed electrician.

How far can you run it? (voltage drop)

Keeping voltage drop under the recommended 3% at a 20 A load (80% of the breaker), 10 AWG copper is good for roughly:

System voltageMax one-way run (10 AWG Cu)
120 V72 ft
240 V144 ft

Past these distances, step up one gauge. Run your exact length and load through the voltage drop calculator.

What runs on 25 amps

  • Small mini-split condensers
  • Hot tub sub-circuits

Frequently asked questions

10 AWG copper with 75°C terminations (NEC Table 310.16, with the NEC 240.4(D) small-conductor cap applied). Aluminum is rarely used at this rating. Longer runs, high ambient temperatures, or bundling can require upsizing.

Ask AI about this

Open an AI assistant with a question grounded in this page.

Full wire & breaker chartVoltage drop calculatorHome electrical load calculator

Other amperages